HYDRONIC FLOW CALCULATOR

Water-side performance  |  Differential pressure  |  Estimated flow
SERVICE ENGINEERING  /  HYDRONICS

Flow measurement worksheet

Enter equipment design data and field readings to estimate water flow through the measured component.

● READY FOR INPUT
01
Design reference
Equipment data
When both design PSI and design head are entered, design PSI is used as the calculation reference. If PSI is blank, design head is converted to PSI using specific gravity.
02
Field measurements
On-site readings
Take pressure readings across the same component using the designated manufacturer test points. Confirm gauge zero and units before calculating.
03
Calculated performance
Live results
Estimated water flow
—
GALLONS PER MINUTE (GPM)
Differential pressure
—
PSI
Differential head
FT OF FLUID
Design flow ratio
—
PERCENT OF DESIGN
Estimated capacity
—
BTU/HR • WATER APPROX.

Design comparison

Measured ΔP / Design ΔP—
Design pressure reference—
Enter the design reference and field readings, then select Calculate Results.
Calculation basis & field-use notice: Estimated flow uses the square-root relationship for a fixed hydraulic resistance: GPM = design GPM × √(measured ΔP ÷ design ΔP). Differential head = PSI × 2.31 ÷ specific gravity. Approximate water-side capacity = GPM × 500 × ΔT. Results are estimates and depend on accurate design data, fluid properties, test locations, and stable operating conditions. Verify against the applicable equipment submittal and manufacturer service documentation. Independent field utility. Not an official Daikin Applied software product; verify results against the applicable equipment submittal and service documentation.